917   Inconsistent DO names for LN DRAT and duplicate DO name DRAT.WRtg

Created: 10 Sep 2012

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page: 45

Clause: 6.1.3

Paragraph:

Category: Issue for edition 2 of this part

Issue

Several data object (DO) name of logical node DRAT do not start with 'Max' although they describe a maximum setting.
Furthermore the data object name 'WRtg' is duplicate. By renaming the first DO 'WRtg' to 'MaxWRtg' this issue can be solved.

Proposal

- Change DO name of DRAT.TmpRtg to DRAT.MaxTmpRtg.
- Change DO name of DRAT.FltARtg to DRAT.MaxFltARtg.
- Change DO name of DRAT.FltDurTms to DRAT.MaxFltDurTms.
- Change DO name of DRAT.VARtg to DRAT.MaxVARtg.
- Change DO name of first occurrence of DRAT.WRtg to DRAT.MaxWRtg.
- Change DO name of DRAT.VarRtg to DRAT.MaxVArRtg.
- Change DO name of DRAT.TmpRtg to DRAT.MaxTmpRtg.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]

Discussion Created Status
30 Jan 14 In Force (green)
Agreed 17 Oct 13 Ballot Period

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1