90   Start a point on wave

Created: 16 Mar 2005

Status: In Force (green)

Part: Part 7-4 (2003)

Links:

Page:

Clause: 5.6.5

Paragraph:

Category: Issue for edition 2 of this part

Issue

A data object to start a point on wave operation using a control service is missing. As for CSWI, there should be the possibility to use a control operation with a data object DPC as an alternate solution to the subscription by CPOW on OpOpn and OpCls from CSWI. If CSWI can use control services for the direct operation using XCBR, whay should it no be possible as well, to use control services for the operation through CPOW.

Proposal

Replace StrPOW with a new data of the CDC DPC.

Discussion Created Status
Voting time expired: accepted 15 Jul 05 In Force (green)
Add new data
Pos(CDC DPC)"Switch position"
in a control section.
Description of CPOW to be updated
02 Apr 05 Ballot Period

 