843   GGIO.AnOut1 move to Controls

Created: 02 May 2012

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 42

Clause: 5.7.3

Paragraph:

Category: Issue for edition 2 of this part

Issue

GGIO.AnOut1 has APC type, but belong to "Measured and metered values" group.

Proposal

GGIO.AnOut1 move to Controls.

Discussion Created Status
Accepted 20 Aug 12 In Force (green)
Add sentence in the description: Analog value (MX) feeds back the setpoint of the output. 20 Jun 12 Discussion (red)
when using APC, the MX constrained value is not really measured. See TISSUE 819 in 7-3.

So I would not create a group "Measured anbd controlled values"
31 May 12 Discussion (red)
Since the DA mxVal is defined as Functional Constraint MX and is listed under “measured attributes and control mirror” within APC, I would recommend to define a new group “Measured and controled values”. So, GGIO.AnOut1 would belong to this group. 30 May 12 Discussion (red)
Accepted. Will be considered. 27 May 12 Discussion (red)

 