800   Misspelling in CSYN

Created: 21 Nov 2011

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 36, 153

Clause: 5,5 and 6/Table 10

Paragraph: 5.5

Category: Issue may impact interoperability of implementations of Edition 2

Issue

1) The abbreviation of intervall in "4 Abbreviated Terms" is Intv and not Inv
Therefore, the "Voltage adjustment interval (in ms)" in CSYN has to be VIntvTmms and not VInvTmms.
2) In the Semantic table 10 (chapter 6)there is only VIntVTms without referring to ms and not correctly VIntvTmms

Proposal

1) Correct in CSYN on page 36 VInvTmms to VIntvTmms

2) Correct in table 10 on page 136 VInvTms into
VIntvTmms "Voltage adjustment pulse intervall in ms"

Discussion Created Status
05 Mar 12 In Force (green)
Accepted. The name will be changed in VIntvTmms. The corresponding entry in table 10 will also be changed in VIntvTmms. 23 Nov 11 Discussion (red)

 