80 TCTR and TVTR - OverCreated: 15 Mar 2005 Status: In Force (green) Part: Part 7-4 (2003) Links: Page: Clause: 5.13 Paragraph: Category: Issue for edition 2 of this part Issue Since TCTR and TVTR can be added to have a over TCTR / TVTR to have single setting, there is a contradiction with the mandatory Amp / Vol which can not be provided by those “Over” transformator logical nodes. Proposal Change Amp / Vol from Mandatory to conditional