781 Max GoCB lengthCreated: 07 Oct 2011 Status: Not Applicable Part: Part 8-1 (2011; Edition 2) Links: Page: 88 Clause: 18.1.1 Paragraph: Category: Issue for edition 2 of this part Issue Part 7-2 clause 22.2 defines the max name length of control blocks to be 32 char. And that FCDA reference shall not exceed 61 char (64 char with FC). The last requirement may restrict the length of the GoCB because the <LN>.GO.<GoCB>.DstAddress.PRIORITY is consuming to much chars. The LN part may be upto 16 chars. As such the GoCB name may only be 24 chars long!
Proposal Keep the restriction that GoCB for LLN0