748   CBOpCap

Created: 01 Aug 2011

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 123

Clause: 6

Paragraph:

Category: Issue for edition 2 of this part

Issue

In the semantic description of CBOpCap is written: "CBOpCap is always less or equal to MaxOpCap.".
This is wrong. CBOpCap is ENS, while MaxOpCap is INS and therefore not comparable.

Proposal

Delete this sentence.

Discussion Created Status
10 Nov 11 In Force (green)
Accepted. Delete this sentence in the semantic table (chapter 6). 12 Oct 11 Ballot Period