744   LN STMP, EEHealth and EEName

Created: 21 Jul 2011

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 95

Clause: 5.14.11

Paragraph:

Category: Issue may impact interoperability of implementations of Edition 2

Issue

In LN STMP the DOs EEHealth and EEName are modelled. This is wrong, because the external equipment for the temperature sensor can be modelles in the LN TTMP if necessary.

Proposal

Remove EEHealth and EEName from LN STMP.

Discussion Created Status
11 Nov 11 In Force (green)
Accepted 12 Oct 11 Ballot Period
accepted 05 Aug 11 Discussion (red)

 