735   ISAF.Alm and ISAF.AlmReset

Created: 26 May 2011

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links: #1568 ISAF.AlmReset ->transient

Page:

Clause: 5.8.4

Paragraph:

Category: Issue for edition 2 of this part

Issue

The semantic of the function Safty function ISAF reg. Alm and AlmReset is not clear. MAy be the AlmReset should be a transient SPC.

Proposal

Explain the use of the data better.

Discussion Created Status
11 Nov 11 In Force (green)
Change of AlmReset to transient is accepted. The attachment will be proposed to include in the future part 7-5. 13 Oct 11 Ballot Period
Controls which resets something (e.g. LEDRs LED reset) send transient feedback signals. Therefore DO AlmReset should be changed to transient(T).
Better explanation gives the proposed use case diagram (for discussion).
15 Sep 11 Discussion (red)

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1