727   RREC - diagram

Created: 05 May 2011

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: annex G

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

Annex G shows functional diagram of the autorecloser.
In the diagram the state "Unsuccessful" is shown twice and the on page 120 written state "Cycle unsuccessful" is missing.

Proposal

Change the value of the last AutoRecSt-state-item (path from Circuit breaker closed with condition "RecCyc >= RecUse/UseCyc") from "Unsuccessful" to "Cycle unsuccessful"

Discussion Created Status
10 Nov 11 In Force (green)
12 Oct 11 Ballot Period
Accepted 19 Jul 11 Discussion (red)

 