689   RREC - diagram

Created: 30 Nov 2010

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: annex G

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

Annex G shows functional diagram of the autorecloser.
In the diagram there is a DO RecUse. This DO doesn't exist in the LN table.
Additionally IEC 61850-7-4 should not define functions normatively.

Proposal

Change annex G to "informative". Change the diagram.

Discussion Created Status
09 Mar 11 In Force (green)
01 Feb 11 Ballot Period
There is no UseRec, but UseCyc. 25 Jan 11 Discussion (red)
10 Jan 11 Ballot Period
Replace the DO name RecUse by UseRec.
Changing annex to informative is accepted.
17 Dec 10 Discussion (red)
13 Dec 10 Discussion (red)

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1