675   SIML LN

Created: 06 Oct 2010

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page: 90

Clause: 5.14.5

Paragraph: Table

Category: Issue for edition 2 of this part

Issue

Data Object InsAlm, SPS, Insulation liquid critical (refill insulation medium), is defined as Mandatory. It needs to be Optional as this information is normally not required or is not available remotely. Few systems will have oil level information connected remotely. As it is Mandatory, every system includes the Data Object but there is no information behind it. That leads to a misleading for clients subscribing to this information as they will think that it is available when it is meaningless.

Proposal

Change to Optional

Discussion Created Status
15 Sep 11 In Force (green)
09 Mar 11 Ballot Period
The semantic description of SIML.InsAlm should be improved. It belongs not only to the level of the insulation medium. So the data object keeps mandatory. 28 Jan 11 Discussion (red)
The basic idea is that if there exists a SIMG at all, it needs InsAlm. Therefore it is mandatory. 09 Dec 10 Discussion (red)

 

Privacy | Contact | Disclaimer