650   MFUL: optional value with mandatory reset

Created: 22 Sep 2009

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page: 80

Clause: 8.1.2

Paragraph:

Category: Issue may impact interoperability of implementations of Edition 1

Issue

Data name 'AccFuel' is optional, while 'AccFuelRs' is mandatory. If one will never implement a read of the value, then why shall one be forced to implement the reset?

Proposal

Change 'AccFuelRs' to optional

Discussion Created Status
Some more comments:
- The name of data objects AccFuel and AccFuelRs have been changed to AccmFuel and AccmFuelRs, resp - see Tissue 922
- The logical node MFUL has been renamed to SFUL and moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1218
- The presence condition of data object AccmFuelRs has been changed to O (optional) in logical node SFUL of IEC 61850-7-4 Ed. 2.1
28 Feb 14 In Force (green)
WG17 decision in Fredericia: change to category "Interop Ed1". 07 Feb 14 In Force (green)
30 Jan 14 In Force (green)
Name changed to AccmFuel and AccmFuelRs
Agree with proposal to change AccmFuelRs to optional
08 Oct 13 Ballot Period

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1