617   IED modelling

Created: 07 May 2008

Status: Not Applicable

Part: Part 6 (2004)

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

how to model an IED as a router?

Proposal

Discussion Created Status
Within SCL the AccessPoint element of an IED has the attributes clock and router to model time synch master clocks and the router function. If an IED is only a router, then just its access point is modelled with the attribute router=true. Observe however that pure routers do NOT talk 61850 and therefore are seldom modeled. If they talk SNMP or another IP based protocol, then edition 2 allows to model them in a SubNetwork with protocol type 'IP'. 07 May 08 Not Applicable

 