614 Protection Scheme HealthCreated: 25 Mar 2008 Status: Not Applicable Part: Part 7-4 (2003) Links: Page: 11 Clause: 4 Paragraph: Not applicable Category: Issue for edition 2 of this part Issue Modeling of old protection schemes to an IEC 61850 environment is no trival task given the detail of data that was previously telemetered and understanding how this relates/equates in a true 61850 environment. Data such as Main & Backup DC Health and Main & Backup Protection Relay health are difficult to model given the lack of sufficient/relating data names. Discrepancy of busbar links are also equally difficult to model. One would prefer more data objects relating to the above information to allow users to model "old" data. Proposal A proposed solution is to implement a new Logical Node namely, RPSH, Related Protection Scheme Health where data as mentioned above and more as others and TC57 experts see fit to include can be modeled. Proposed new Data Names adhereing to the abbreviation convention in 7-4 (clause 4) and to be used in conjunction with LN RSPH and other LN as seen fit are as follows: