606   PF tests

Created: 19 Feb 2008

Status: Triage

Part: Part 3 (2003)

Links:

Page: 23

Clause: 5.7.3

Paragraph:

Category: Issue for edition 2 of this part

Issue

Clause 5.7.3 mentions that (power frequency) magnetic fields are to be performed according IEC 61000-4-8 and IEC 61000-4-10. The test values according IEC 61000-4-8 and IEC 61000-4-10 are not mentioned.

Proposal

Split clause 5.7.3 in the following subclauses

5.7.3.1 Conducted common mode power frequency disturbances

see table 1

5.7.3.2 Power frequency magnetic fields

100 A/m continuous and 1000 A/m 1 s.

5.7.3.3 Damped oscillatory magnetic fields

3 A/m continuous and 30 A/m 1 s.