588   GAPC for modelling generic automation functions

Created: 19 Dec 2007

Status: In Force (green)

Part: Part 7-4 (2003)

Links:

Page: 44

Clause: 5.7.1

Paragraph:

Category: Issue for edition 2 of this part

Issue

GAPC should be used to model in a generic way automation function not covered by LNs A,C,M,P,R. But GAPC contains the mandatory objects Str (ACD) and Op (ACT) which cannot be used for non-protection-related automation functions.

Proposal

Set Str/Op to "Optional" (O).

Discussion Created Status
07 Feb 08 In Force (green)
In IEC 61850-7-4 Ed.2 CD(committee draft) Str and Op are already optional. 19 Dec 07 Ballot Period

 

Privacy | Contact | Disclaimer