Operate as CDC DPC makes no sense. Feedback value can never be “intermediate“

Proposal

Change to CDC SPC

Discussion Created Status
Operating SPC is like DPC: Writing Oper.ctlVal=TRUE sets TRUE/ON, writing FALSE sets FALSE/OFF. No reason for two controls... 19 Oct 07 Discussion (red)
By changing to SPC, we need two controls, one for on and one for off. 19 Oct 07 Triage

 