552   HMBR-Controls

Created: 15 Oct 2007

Status: Discussion (red)

Part: Part 7-410 (2007; Hydro Power)

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

HMBR.Pos is indicated as DPC

Proposal

Should be SPC

Discussion Created Status
Operating SPC is like DPC: Writing Oper.ctlVal=TRUE sets TRUE/ON, writing FALSE sets FALSE/OFF. No reason for two controls... 19 Oct 07 Discussion (red)
If we change to SPC, we need two controls, one to engage the brake and a second to disengage the brake. It seems simpler to keep the function as DPC. 19 Oct 07 Triage

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1