551   LN HGPI

This tissue has following status: green

Created: 15 Oct 2007

Links:

Page:

Clause: 7.3.6

Paragraph:

Category: Issue for edition 2 of this part

Issue: The units for GtePos are unspecified and the inplied 0.05 degree unit is very non-standard.

Proposal: Specify unit as degrees

Discussion Created Status
?
Ballot until Editor
Agreed. The original unit was based on a swedish practice where sector gates always have a radius of 11,5 meters. This will have the result that 1/20 degrees corresponds to a movement of 1 cm along the periphery.

If the gate has a different radius, 0,05 degrees just makes no sense.
19 Oct 07 white

 

Privacy | Contact | Disclaimer