537   Timer for control model

Created: 07 May 2007

Status: Not Applicable

Part: Part 7-2 (2003)

Links:

Page: 142 & 145

Clause:

Paragraph: §17.2.2 & 17.3.3

Category: Issue for edition 2 of this part

Issue

1/ In §17.2.2,the part a) of the Procedure references an attribute SelTimOut whose name is never referenced (either in IEC 61850-7-2 or in IEC 61850-7-3).

2/ In §17.3.3, the part a) of the Procedure references an attribute sboTimOut whose name is not correct according to IEC 61850-7-3.

Proposal

1/ No proposal...

2/ Replace in the text "sboTimOut" by "sboTimeout".

Discussion Created Status
Fixed in Ed2.
SelTimeout has been changed to sboTimeout
20 Feb 09 Not Applicable
Accepted.

1/ wait for proposal by editor of part 7-3 (CDCs)

2/ Name changed.
17 Feb 08 Discussion (red)

 

Privacy | Contact | Disclaimer