502   Get/SetDataValue(s) with multiple references

Created: 13 Apr 2007

Status: In Force (green)

Part: Part 7-2 (2003)

Links:

Page: 53

Clause: 10.4.1

Paragraph: Figure 14

Category: Issue for edition 2 of this part

Issue

In the figure 14 the services GetDataValue/SetDataValue seem to hold more than one reference in the request.

The service parameter table of the GetDataValue/SetDataValue service in clause 10.4.2.1/10.4.3.1 only specifies one Reference (not an array of references as Reference[1..n])in the request.

Proposal

Modify the Figure 14 to describe clearly that only one reference is sent in each service ACSI-Get/SetDataValue-Request.

Discussion Created Status
Accepted.
Editorial proposal has been implemented.
Changed status to green.
14 Apr 07 In Force (green)

 