478 emergency off, IHMI.EmgOffCreated: 08 Mar 2007 Status: In Force (green) Part: Part 7-4 (2003) Links: Page: 46 Clause: 5.8.2 Paragraph: Category: Issue for edition 2 of this part Issue Actually some HMIs have some kind of emergency pushbuttons, that interrupt immediatly running control actions, for example a running load tap changer: If the button is pushed, the drive of the load tap changer stops running immediatly. If this information is not transmitted by a separate wire, but over a process bus, there is no data in the standard to model that. A new data, that is transmitted by a GOOSE-message, should be added.
Proposal Add new data: