469   oper timeout missing in controlable CDC

This tissue has following status: green

Created: 09 Feb 2007

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue: The controlable CDCs do not contain a configuration attribute for the run time supervision of the controlled object.

Proposal: Similar to the sboTimeout, add an operTimeout CF attributes to controlable CDC. This attribute is conditional optional for the case where the control model is with enhanced security. It contains the supervision time for the run time of the controled object. A timeout would lead to an additional cause time-limit-over.

Discussion Created Status
?
Ballot until Editor
Accepted. operTimeout attribute (FC = CF, AC_CO_O), dataType INT32U will be added to SPC, DPC, INC, BSC, ISC, APC 09 Feb 07 final proposal 2007-03-09

 