46 Synchro check cancelCreated: 15 Mar 2005 Status: In Force (green) Part: Part 7-2 (2003) Links: Page: Clause: 17.3.3 Paragraph: Figures 33, 34 Category: Issue may impact interoperability of implementations of Edition 1 Issue For the synchro-check functionality it is necessary to cancel the command sequence after an oper_req command is given. In this case the synchro-check is running and waiting for the switch on conditions (frequency, voltage has to be within the permitted range) Relating to the given state machine this status is in between “ready” and “WaitForChange” waiting for Oper_resp +. Proposal GoE-meeting 28.10.04: