454   lnClass and lnType relationship

Created: 13 Dec 2006

Status: Not Applicable

Part: Part 6 (2004)

Links:

Page:

Clause: 9.3.5

Paragraph:

Category: No impact on this part

Issue

Just a question. Within the scope of the same IED, could two LN instances with identical lnClass have different lnType?

Proposal

Clarify.

Discussion Created Status
yes, nothing forbids this - and it is often needed; for example you might have CSWI for disconnectors and earthing switches, jhowever the earthing switches are only locally controllable - then their CSWI might have another lnType. 14 Dec 06 Not Applicable

 