438 EntryTime base should be GMT
Created: 01 Nov 2006
Status: In Force (green)
Part: Part 8-1 (2004)
Links:
Page: 36
Clause: 8.1.3.7
Paragraph:
Issue: EntryTime maps to MMS BINARY-TIME, but the timezone for MMS BINARY-TIME has never been clear (local or GMT). This has caused confusion in many existing MMS applications.
Proposal: This clause should clearly state that EntryTime is based on GMT.
Discussion |
Created |
Status |
changed to green.
|
16 Feb 07 |
In Force (green) |
Changed to final proposal.
|
10 Nov 06 |
Ballot Period |
I agree that the time basis for EntryTime should be GMT. The following sentence should be added in F.1 and 8.1.3.7
"The MMS TimeOfDay epoch began at 0 hours on 1 January 1984 (MJD 40 587). Times measured are designated in this standard as MMS TimeOfDay milli-seconds GMT and TimeOfDay days GMT, and represent offets from the epoch."
|
01 Nov 06 |
Discussion (red) |