397   Use of 3x TCTR vs. 3xSMV in one TCTR

Created: 15 Sep 2006

Status: In Force (green)

Part: Part 7-4 (2003)

Links:

Page: 60 and 91

Clause: Annex A.3

Paragraph:

Category: Issue for edition 2 of this part

Issue

Annex A.3 gives the method to multiply the DO with number extensions. It is normative to model 3 samples within 1 TCTR/TVTR or it is only allowed to use three TCTR/TVTR (acc. 9-2LE)?

Proposal

Give a modelling example for that in edition 2.

Discussion Created Status
Balloting time over 27 Oct 06 In Force (green)
There exist phase related LNs. Using these in a three-phase system means always to have 3 instances if these Logical Nodes (see Annex A2). In this case the extension rules according to Annex A3 are not applicable. Proposal: For clarification, improve description of the LNs and of the Annex A2 and A3 where necessary. 25 Sep 06 Ballot Period

 