350   CONTROL class model makes no references to LNs

Created: 24 Jul 2006

Status: Not Applicable

Part: Part 7-2 (2003)

Links:

Page: 136, ..

Clause: 17

Paragraph: 17.1

Category: Issue for edition 2 of this part

Issue

In clause 17 no reference is made to LNs where the CONTROL services reside. E.g. the controllable data attributes in data DPC exist as well for switch contoller CSWI as for XCBR and XSWI. All figures, e.g. figure 36 and 36 do not show that the CSWI controls the XCBR and XSWI (with possible different communication services client/server and GOOSE).

In paragraph 17.5.2.1 it is not clear which ControlObjectReference to for example POS is meant, POS in CSWI or in XCBR and XSWI?

Proposal

Extend the description to clarify the problem described above.

Discussion Created Status
rejected. The issue where a control service resides is an application issue, may be even a project specific issue, and does not belong into 7-2. For the same reason it does not matter if the Pos resides in an CSWI or an XSWI. The important point here is just, that the object reference is a DATA reference. 04 Aug 06 Not Applicable

 