288   RDRE.RcdTrg

Created: 06 Feb 2006

Status: In Force (green)

Part: Part 7-4 (2003)

Links:

Page: 36

Clause: 5.5.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

RDRE.RcdTrg allows to trig a recorder with an external command. But there is a need for a client to specify the duration of the triggered record.

Proposal

Change the attribute type of RDRE.RcdTrg from SPC to INC.
Change the definition of RDRE.RcdTrg for :
"External command to trigger recorder. The value sent is the duration of the triggered record in milliseconds".

Discussion Created Status
Final proposal accepted. No change. 08 Jun 06 In Force (green)
Since it was refused in the last WG10 meeting in Merida and no new comments came up, this non accpetance is set as final proposal for voting. 14 May 06 Ballot Period
Not accepted since function already exists using two commands. 30 Mar 06 Discussion (red)

 