262   LastApplError Error codes

Created: 18 Nov 2005

Status: In Force (green)

Part: Part 8-1 (2004)

Links:

Page: 88

Clause: 20.8

Paragraph:

Issue: Part 8-1 defines LastApplError to have component named Error and its ENUM values. It is however not defined how these values should be used.

Proposal:

Discussion Created Status
changed to green 13 Jan 06 In Force (green)
The text should be modified to indicate:

TimeOut Test Not OK shall be returned if a TimeActivated Control CMD is issued, with TEST=TRUE, and the operation fails.

Operator Test Not OK shall be retunred if an OPER control CMD is issued, with TEST=TRUE, and the operation fails.
02 Dec 05 Ballot Period
When to use LastApplError is defined in IEC 61850-7-2. In 61850-7-2, this is detailed as AddCause.

Therefore, to find out when to send 8-1's LAstApplError, 7-2 is the specification.
18 Nov 05 Not Applicable

 

Privacy | Contact | Disclaimer