262 LastApplError Error codes
Created: 18 Nov 2005
Status: In Force (green)
Part: Part 8-1 (2004)
Links:
Page: 88
Clause: 20.8
Paragraph:
Issue: Part 8-1 defines LastApplError to have component named Error and its ENUM values. It is however not defined how these values should be used.
Proposal:
Discussion |
Created |
Status |
changed to green
|
13 Jan 06 |
In Force (green) |
The text should be modified to indicate:
TimeOut Test Not OK shall be returned if a TimeActivated Control CMD is issued, with TEST=TRUE, and the operation fails.
Operator Test Not OK shall be retunred if an OPER control CMD is issued, with TEST=TRUE, and the operation fails.
|
02 Dec 05 |
Ballot Period |
When to use LastApplError is defined in IEC 61850-7-2. In 61850-7-2, this is detailed as AddCause.
Therefore, to find out when to send 8-1's LAstApplError, 7-2 is the specification.
|
18 Nov 05 |
Not Applicable |