Issue

Part 8-1 defines LastApplError to have component named Error and its ENUM values. It is however not defined how these values should be used.

Proposal

Discussion Created Status
changed to green 13 Jan 06 In Force (green)
The text should be modified to indicate:

TimeOut Test Not OK shall be returned if a TimeActivated Control CMD is issued, with TEST=TRUE, and the operation fails.

Operator Test Not OK shall be retunred if an OPER control CMD is issued, with TEST=TRUE, and the operation fails.
02 Dec 05 Ballot Period
When to use LastApplError is defined in IEC 61850-7-2. In 61850-7-2, this is detailed as AddCause.

Therefore, to find out when to send 8-1's LAstApplError, 7-2 is the specification.