205   Device name plate - missing description "d" and "dU"

Created: 14 Sep 2005

Status: In Force (green)

Part: Part 7-3 (2003)

Links:

Page: 49

Clause: 7.9.2

Paragraph: table 46

Category: Issue for edition 2 of this part

Issue

The device name plate common data class "DPL" does not contain a description data "d" and "dU". For example there is no way to describe the external equipment ... in addition to the model (of type VISIBLE STRING255) which precludes unicode characters.

Proposal

Add "d" and "dU" in the "DPL" common data class.

Discussion Created Status
no negative comment received on voting; set to green 17 Nov 05 In Force (green)
Final proposal
Add "d" and "dU" in the DPL CDC as optional attributes
10 Oct 05 Ballot Period
I support that 03 Oct 05 Discussion (red)
I agree, but both should be optional. 20 Sep 05 Triage

 