20   Store settings values

Created: 30 Jan 2005

Status: Not Applicable

Part: Part 6 (2004)

Links:

Page:

Clause: 9.3.12

Paragraph:

Category: No impact on this part

Issue

We have not found by any way how to store via the .SCD file the values of parameters for each setting group block. We do not know if it is a misunderstanding. If not, it will not be possible to have as standardized way the values for the different setting groups in order to automate the download for both configuration and parametrization. It it is done manually on-line, and then, the stored information need to be kept in a private extension of the .CID file

Proposal

To extend the possibilities for defining each value for each parameter within each setting group.

Discussion Created Status
The possibility is already defined: See definition of "sGroup" in "Val" (clause 9.5.4.4). "sGroup" specifies the number of setting group to which this value belongs.
Set to blue.