1881 Missing Downgrading rule for MV.mag with data-updateCreated: 21 Jul 2023 Status: Discussion (red) Part: Part 6 (2019; Edition 2.1) Links: Page: 253 (CSV) Clause: I.2.1.4 Paragraph: Incompatible CDCs Issue IEC61850-7-3 Ed2 has introduced the choice of trigger option: dchg or dupd for INS.stVal, MV.mag, CMV.cVal. Those attributes where defined with dchg only in IEC 61850-7-3 ED1. ENS.stVal offers also the choice dchg or dupd for ENS.stVal. ENS is downgraded to an INS according to I.2.1.2.
Proposal Provide an additional downgraded rule for the incompatible CDC:
Privacy | Contact | Disclaimer Tissue DB v. 23.8.4.2 |