1858   Usage of Beh test/blocked when performing protection tests

Created: 06 Jan 2023

Status: Editorial

Part: Part 7-1 (2020; Edition 2.1)

Links:

Page: 62, 66

Clause: 7.7.3, 7.8.4

Paragraph: 7

Issue

The paragraphs illustrate very basically the usage of Beh during test.
During InterOp it was noticed that the "test/blocked" behavior is offering limited test capability when performing protection testing.
Usage of test/blocked can allow to measure the transmission time to the breaker.
But the subscribing protection (autorecloser, breaker failure, pole discrepancy, …) need to receive an updated position to proceed with further protection measures.

Proposal

Consider updating 10-3 with regard to usage of Beh test/blocked, and consider updating the clause to indicate that in case of test, when the breaker is in test/blocked, the subscribers IEDs need most likely to be in simulation state and get a breaker position after a trip that match the scope of the test from the breaker simulator.

Discussion Created Status
Approved Editorial

Note the proposed change can be found in the attachment from the comment of May 2, 23
12 Dec 23 Editorial
Set to Editorial as this is a clarification. 17 Oct 23 Approval (Editoral)
Should this be Editorial? 17 Oct 23 Discussion (red)
No Comment, move to next state 17 Oct 23 Analysis Of Compatibility
for review 22 Aug 23 Verify Draft Implementation
accepted 22 Aug 23 Drafting Implementation
Open for discussion 11 Jul 23 Discussion (red)
See attached proposal 02 May 23 Accepted
Accepted: Expand 7.7, 7.8 to describe the use of test/block in protection testing. 28 Feb 23 Accepted

 