1857   Concept of smpRate for input analogue signal acquisition is misleading

Created: 20 Dec 2022

Status: Editorial

Part: Part 7-1 (2020; Edition 2.1)

Links: #1840 The role of smpRate of MV/CMV

Page: 40

Clause: 6.4.3.1

Paragraph: 6.4.3.1

Issue

The conceptual specification indicates:
"The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled."

1) SAV CDC does not contain a data attribute smpRate
2) The Txxx.SmpRte data object indicates how often the value has beeen sampled.
3) the MV/CMV.smpRate attribute inidcates how often the sample has been observed for actualizing the inst component.

Proposal

Modify the clause 6.4.3.1 to indicate that:
The Txxx.SmpRte data object indicates how often the value has beeen sampled.

see tissue #1840

Discussion Created Status
Approved Editorial 12 Dec 23 Editorial
Editorial change:

Modify the clause 6.4.3.1:

Replace:
The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled.

With:
The Txxx.SmpRte data object indicates how often the value has been sampled.
22 Aug 23 Approval (Editoral)
This is not a change in CDC, many settings are not writable.

This is an editorial change, following the linked tissue.

22 Aug 23 Approval (Editoral)
TPWG:

Is this a FC change?

SmpRte is ING - setting. Change to INS?
25 Jul 23 Discussion (red)
NO issues found, move to CTP 11 Jul 23 Conformance Test Preparation
No objection, proceed to next state. 09 Jun 23 Analysis Of Compatibility
Modify the clause 6.4.3.1:

Replace:
The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled.

With:
The Txxx.SmpRte data object indicates how often the value has been sampled.
02 May 23 Verify Draft Implementation

 

Privacy | Contact | Disclaimer