Issue

The description text of 'PMRI.StrIhnTmm' goes
"Actual remaining time to restart inhibition".

This means: remaining time until a blocking will be activated.

Is this the intended semantic?

Proposal

Please clarify whether the intended semantic is

"remaining time until a blocking will be activated" (as the existing text tells)
or whether it should be

"remaining time until an active blocking will be released".


'InhTmm' specifies the overall inhibition time. A data giving the remaining waiting time until release is not standardized, but is required by users.

Discussion Created Status
Ballot period expired without comment.
Move to solution accepted.
21 Dec 23 Solution Accepted
Starting ballot period 15 Nov 23 Ballot Period
No impact on conformance testing. 14 Nov 23 Conformance Test Verification
Change to state: Conformance Test Preparation 17 Oct 23 Conformance Test Preparation
The technical error does not address any of the use cases of Part 7-1, Annex K. It is an improvement of the description text.

In summary: no compatibility issue.
10 Oct 23 Analysis Of Compatibility
Draft of implementation is attached. New description of StrInhTmm is marked in yellow. 26 Sep 23 Verify Draft Implementation
Change to Drafting Implementation state 19 Sep 23 Drafting Implementation
I support the proposal : Change description of DO PMRI.StrInhTmm from "Actual remaining time to restart inhibition" to "Remaining time until an active blocking will be released".
Presence condition and CDC will be kept.
26 Jun 23 Discussion (red)
The understanding as per latest proposal is welcome. It fulfils the user requirements.

I propose to modify to "remaining time until an active blocking will be released".

I recommend to not use "actual remaining time to restart" since we do not know whether the motor will be restarted automatically.
15 Mar 23 Accepted
After verification with motor protection expert, the intention of StrInhTmm is to expose the time remaining until a motor can be started again.
Therefore
"remaining time until an active blocking will be released"
or
"actual remaining time to restart"
could provide a clarified semantic.
15 Mar 23 Accepted
There are other DO we have to consider (as I understand the function):

StrInh - If true, the restart has been inhibited (as a consequence of reaching a limit, for example maximum number of starts or permissible temperature).
InhTmm - Limit for restart inhibition time 'StrInhTmm'. Once the restart has been inhibited ('StrInh'=true), the motor should not be allowed to start until this time has elapsed.

I agree the wording of StrInhTmm might be not clear. I would suggest to change: "Actual remaining time of restart inhibition."
("of" instead of "to").

Does it make sense? Motor protection experts, pls confirm or commment if you have a different opinion.
09 Dec 22 Accepted

 