1851   Trigger option 'dchg' for settings of FC=SG

Created: 11 Nov 2022

Status: Editorial

Part: Part 7-3 (2020; Edition 2.1)

Links:

Page: 78 ff. of INF

Clause: 7.6 & 7.7

Paragraph: Tables 49 ff.

Issue

Reference is made to Tissue #204.

Despite Tissue #204, setting attributes of FC=SG do not have a trigger option.

Changing a setting value of FC=SE will not be reported (ok).

When changing the active setting group, the values of all settings of FC=SG will be updated. Due to the fact that these attributes do not have trigger options, the coming active of different setting values due to a change of the active setting group cannot be reported.

Proposal

Add the trigger option 'dchg' to attributes FC=SG.

Discussion Created Status
Approved 20 Dec 22 Editorial
Move to Approval Editorial as disussed on Nov, 22nd 20 Dec 22 Approval (Editoral)
Propose to add clarification in STS that the serviceType "SelectActiveSG", "SelectEditSG" or "ConfirmEditSG" shall be used as well when those activities were initiated not using IEC 61850 service but local means like through the HMI of the IED.

Propose to make Editorial TISSUE
22 Nov 22 Triage

 

Privacy | Contact | Disclaimer