1802   Equipment Problem with CB Operating mechanism

Created: 06 Dec 2021

Status: Future Improvement

Part: Part 7-4 (2020; Edition 2.1)

Links:

Page: 306

Clause: 6.14.7

Paragraph: Table 157

Issue

The LN SOPM provides multiple alarms for various problems of the Operating mechanism but does not have a DO EEHealth.

Proposal

Add a DO EEHealth to SOPM (and possibly all condition monitoring LNs) to provide the possibility to have a summary alarm of the Equipment part that is supervised by that LN

Discussion Created Status
accepted future 25 Oct 22 Future Improvement
Agree to change to future improvement (i.e. will be solved with next version of the standard). Be aware, that we have in TF 90-3 an ongoing discussion about the so called Health Index acc. CIGRE Technical Brochure 858. 24 Oct 22 Approval (Future Improvement)
Agree that EEHealth may not be the right solution as indeed SOPM is the monitoring function and not the interface to the operating mechanism.

So proposal would then be to add in addition to the individual alarms a new DO as a general alarm for the operating mechanism.

Proposal to make this a future TISSUE
11 Oct 22 Discussion (red)
Change to "Not Applicable" 20 Dec 21 Approval (N/A)
It is not the intention of SOPM to represent the primary equipment function and resp. EEHealth for the external equipment health. SOPM is just the monitoring function.
I would propose to model both LNs, SOPM to detect alarm/warning conditions and XCBR/XSWI with EEHealth to show the summary health status.