1706   Missing LN for Miniature Circuit Breaker (MCB)

Created: 29 Jul 2020

Status: Future Improvement

Part: Part 7-4 (2020; Edition 2.1)

Links:

Page: 344

Clause: 6.16.3

Paragraph: XFUS

Issue

Missing Logical Node for moddeling a Miniature Circuit Breaker (MCB). A MCB can be operated many times compared to XFUS which only can opened once, as stated in 6.16.3.

Proposal

Make a Logical Node for a MCB.

Discussion Created Status
Future Improvement 27 Oct 20 Future Improvement
The requirement is accepted. We have already discussed the need for a LN of MCB in WG10 in the last meeting. we have decided to work on it (within a model of auxillary power network).
The model of MCB is not an interoperability issue. So I suggest to state it as "Future improvement".
29 Jul 20 Triage

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1