1673 Configuration interoperability with IEC 61850-9-2 LE subscribersCreated: 17 Feb 2020 Status: Future Improvement Part: Part 6 (2019; Edition 2.1) Links: Page: 103 Clause: 9.3.11 Paragraph: Table 29 Issue Ed2 has introduced for SampledValueControl the property smpMod. The interpretation of smpMod is necessary to understand the content of smpRate.
Proposal SampledValueControl block shall be configured with smpMod = smaplePerPeriod when configuring SampledValueControl subscribed by IEC 61850-9-2 LE subscribers.
Privacy | Contact | Disclaimer Tissue DB v. 23.3.6.1 |