1673   Configuration interoperability with IEC 61850-9-2 LE subscribers

Created: 17 Feb 2020

Status: Accepted

Part: Part 6 (2019; Edition 2.1)

Links:

Page: 103

Clause: 9.3.11

Paragraph: Table 29

Issue: Ed2 has introduced for SampledValueControl the property smpMod. The interpretation of smpMod is necessary to understand the content of smpRate.
Using smpMod != sample per period leads to interoperability problems with IEC 61850-9-2 LE subscribers, that only know the sample rate attribute and not the sample mod.

Proposal: SampledValueControl block shall be configured with smpMod = smaplePerPeriod when configuring SampledValueControl subscribed by IEC 61850-9-2 LE subscribers.

Additionally, new serviceCapabilities shall be introduce to indicate what the supported MU variant supported by IEC 61869-9 subcribers.

Discussion Created Status
a clear definition of compatibility rules have to be added related to new capabilities 02 Mar 20 Accepted

 