1591   Pst used inconsistently

Created: 14 Jul 2017

Status: In Force (green)

Part: Part 90-17 (2017; Ed1, Power Quality Data)

Links:

Page:

Clause:

Paragraph:

Category: Issue may impact interoperability of implementations of Edition 1

Issue

In "Table 8 – PQ records for Class A and Class S devices", flicker is mentioned as both short term (Pst) and long term (Plt). The same notation is used in "Figure 21 – State of the art data modeling for use case “Request for power quality
measurements”."

However in the enumerated data types of section 7.5 and the SCL enumerations of Annex A the term Plt is used for both short term and long term flicker. This is present in "Figure 31 – Enumerated data attribute types", "Table 49 – Literals of FlickerCalcMethodKind" and "A.1
SCL enumerations (from DOEnums_90_17)"

Proposal

Change:

"Short term flicker Plt"

to

"Short term flicker Pst"

Discussion Created Status
Change to green 29 Sep 17 In Force (green)
Changed to final proposal. 30 Aug 17 Ballot Period
You are right. Copy/paste error.
Change literal to "Short term flicker Pst" - value 1