1479   Sending BitString Data in the GOOSE message

Created: 03 Mar 2016

Status: Not Applicable

Part: General

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

Is it possible to send 32bit bitstring data in a GOOSE message,if so which CDC will suits for this requirement.

Proposal

Discussion Created Status
No. IEC 61850 is object-oriented. So a 32-bitstring doesn't make sense.
Using INS (INT32) will be a private solution.
An interoperable and standardized solution would be to use 32x single point information (SPS).
04 Mar 16 Not Applicable

 