1430   opRcvd for controllable object

This tissue has following status: green

Created: 05 Aug 2015

Links:

Page: 68

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue: In semantic table DO opRcvd is only for indication that an operate command for a controllable DO has been received. But if XCBR is realized as breaker IED at the switchyard and CSWI sends GOOSE messages (OpOpn/OpCls) to XCBR. Must XCBR generate opRcvd? And if i want to test protection node without trip command to process and i want to be sure that XCBR receives trip command but it doesn`t operate, may i use opRcvd?

Proposal:

Discussion Created Status
?
Ballot until Editor
22 Nov 15 green
Final Proposal:
Text will be improved as follow (change first sentence):
The command is received ('opRcvd') by the IED as a control service or as a GOOSE message with a data object semantic resulting in a change of the controllable object (e.g. CSWI.OpOpn/OpCls, CPOW.OpOpn/OpCls, PTRC.Tr, RREC.OpCls, RBRF.OpEx, ATCC.TapOpR/TapOpL, SIMG.InsTr, ...)

Note: the test according to annex E of the UCA testing guideline need to be extended
22 Oct 15 final proposal 21. Nov 2015
I agree with the proposal:
Tr is a data object that is interpreted as an 'operate' request on the controllable object, and therefore shall be mirror by the opRcvd, opOk, tOpOk as well as OpOpn, OpCls.

06 Aug 15 red
The opOk will be performed by XCBR.Pos. So the control by OpOpn can be by checked.
Future technical report IEC 61850-7-500 gives an example.