1408   regarding Report Control Block

Created: 10 Jun 2015

Status: Not Applicable

Part: General

Links:

Page: 74

Clause: 14.2

Paragraph: second

Category: No impact on this part

Issue

I am new in IEC 61850 . I am facing RCB connecting with SCADA software. when I enable RCB. I did not get any data on SACDA software. I took the wirshirk log. Please refer the attach image. Please let me know whats going wrong.

Thanks in Advance.

Proposal

Discussion Created Status
Dear Ankur,
the purpose of this page is to document issues in the standard IEC 61850. This is not a help desk for implementation. Thanks for your understanding.

We should close that TISSUE.
30 Jun 15 Not Applicable
Dear Ankur,

the server response for q is incorrect (bytes 84 01 00). It should return something like 84 03 03 00 00. Is the server conformance tested with certificate?
10 Jun 15 Triage

 