1395   Client LN attributes

Created: 02 Jun 2015

Status: In Force (green)

Part: Part 6 (2009-12; Edition 2)

Links:

Page: 78

Clause: 9.3.8

Paragraph:

Category: Issue may impact interoperability of implementations of Edition 2

Issue

From TF User Feedback / IOP 2013

The actual format required for an ClientLN (used for ReportControl Block reservation) is not specified fully or in an understandable way.
LDInst is required, but for Client only IEDs, there is no LD. The standard indicates to select a random LDInst and provides some guidance. However, in order to insure that there is interoperability and that importers understand that there is NO LDInst, the value to indicate this needs to be standardized.

Proposal

Proposal to modify part 6, that curretnly recommends to use LD0 in a "shall use LD0"

Discussion Created Status
07 Jul 15 In Force (green)
Will be applicable in Ed 2.1 of IEC 61850-6
Agree that we request the usage of LD0 as required in the described case.