1348   Fuse model

Created: 05 Feb 2015

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

It is required to have a LN for fuses with status signal.

Proposal

Model XFUS with status signal and descriptive information in nameplate.

Discussion Created Status
Change to green 16 Sep 15 In Force (green)
For the CDV of amendment 2.1 of part 7-4 we propose to model XFUS with:
FuSt SPS If true, fuse has operated (interrupted). O / F
FuTyp ENG (FuseFunctionKind) Type of fuse. M / F
ARtg ASG Current rating. O / F
VRtg ASG Voltage rating. O / F

11 Aug 15 Ballot Period
The function of XFUS is still not clear. I suggest to include as a first definition the LNclass XFUS with three DO: FuSt(SPS, optional, If true, fuse is interrupted, otherwise ok); VRtg (ASG, optional, Rated voltage), ARtg (ASG, optional, Rated current).
The discussion will be continued by commenting the CDV.
27 Jul 15 Discussion (red)
Back to red state because of discussion with WG17 UML TF. 04 May 15 Discussion (red)
The tissue goes to "final proposal" with the following specific DO:
FuSt SPS If true, fuse is interrupted O / F
19 Feb 15 Ballot Period
Will be considered in amd 2.1
The status signal will be SPS.
05 Feb 15 Discussion (red)

 

Privacy | Contact | Disclaimer

Tissue DB v. 23.12.13.1