1330   proposal in tissue 830 seems not consistent with 7-3 Ed2

Created: 14 Nov 2014

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links: #1331 Mod, Beh and Health with q=TEST, client can't receive their states , #830 Mode/Behaviour & Quality

Page: 157

Clause: Annex A

Paragraph:

Category: Issue for edition 2 of this part

Issue

In tissue 830 a proposal has been accepted:

"Incoming data with q=test+operatorBlocked means validity=good AND test=True AND operatorBlocked=True".

But in IEC61850-7-3, page 14 paragraph 6.2.6, if a data is frozen by operator, so identifier "oldData" shall be set. And according detail quality table, if identifier "oldData" is set, quality has to be "questionable".

Proposal

Modify "Incoming data with q=test+operatorBlocked means validity=good AND test=True AND operatorBlocked=True" by "validity=questionable AND test=True AND operatorBlocked=True".

Discussion Created Status
Voting finished and went to green 20 Jan 15 In Force (green)
Changed to Final Proposal 18 Dec 14 Ballot Period
Agree. Additionally change line in tissue #830:

"Incoming data with q=operatorBlocked means validity=good AND test=False AND operatorBlocked=True" by

"Incoming data with q=operatorBlocked means validity=questionable AND test=False AND operatorBlocked=True"

So in draft of amendment v2.1 part 7-4, annex A, table A.2 two lines will be changed.