1292   Voltage differential protection

Created: 30 Jul 2014

Status: In Force (green)

Part: Part 7-4 (2010; Edition 2)

Links:

Page:

Clause:

Paragraph:

Category: Issue for edition 2 of this part

Issue

The protection function voltage differential protection (87V) is missing. It is used for capacitor unbalanced function to detect internal C-element faults.

Proposal

Add the data model for voltage diiferential protection as given in the attached proposal.

Discussion Created Status
As a summary the agreed new LNclass for revision 2.1 of part 7-4 is provided in an attachment. The tissue goes to green. 30 Oct 14 In Force (green)
The proposal with extension in the discussion has been agreed. So I change it to status "Final proposal". 10 Oct 14 Ballot Period
87V is the voltage differential protection. PTDV can be used for unbalanced voltage protection between phases. A typical application is the protection of capacitor banks. The description of PTDV shall express this. 10 Sep 14 Discussion (red)

 