1280   Services: TimeSyncProt

Created: 08 Jul 2014

Status: In Force (green)

Part: Part 6 (2009-12; Edition 2)

Links: #1359 Replace "c37_238" with "61850-9-3"

Page:

Clause: Tissue 789 / Table 11

Paragraph:

Category: No impact on this part

Issue

Tissue 789 extended the capabilites with (among others) Services/TimeSyncProt and Services/ClientServices/TimeSyncProt.
Valid attributes are sntp, c37_238, and other.
The final WG10 decision on a specific 1588 profile will not be taken until November 2014. In order not to delay part 6 unnecessarily, and to make the protocol information more general as "kind of time sync (technology)" instead of a specific profile, the attribute value c37_238 should be changed.

Proposal

Change the attribute value c37_238 (Tissue 789) for Services/TimeSyncProt and Services/ClientServices/TimeSyncProt into IEEE1588.

Discussion Created Status
Tissue not relevant anymore - see solution of Tissue 1359 instead 01 Jul 15 In Force (green)
disagree to rename attribute for backward compatibility reason as defined in Part 6 chapter 8.2
Therefore, I propose to leave c37.238 and to add in a future release of SCL the other ptp profiles.
A future version of scl, including new profiles can declare obselete the use of the attribute c37.238 as specified in Part 6 chapter 8.2.
23 Jul 14 Discussion (red)

 